Why the tag matters as much as the symbol
Notification appliances are sold in versions: a horn/strobe comes in several candela ratings, in wall and ceiling bodies, and in a weatherproof model for the loading dock. The symbol on the plan is the same for all of them; the difference is a small label beside it. Material, listing and labour all follow the label, so the takeoff has to.
Detection has its own split: a duct smoke detector is a different device from a spot smoke detector, mounted in the duct with a housing and often a remote test switch, and the drawing marks it with a small change to the same hexagon.
The attributes, one by one
Candela
Strobe output is rated in candela (cd), and the common values on drawings are 15, 30, 75 and 110, with 60, 95, 135, 177 and 185 appearing on some manufacturers' sheets. The value is written beside the device ("30CD", "75 cd", sometimes just the number) or carried by a tag the legend defines. Two strobes with different candela are two different parts, and a takeoff that reports "strobes: 42" has pushed that split onto whoever orders the material.
Wall or ceiling
Wall and ceiling appliances have different bodies and different lenses, and on most sets a ceiling device is marked with a C beside or inside the symbol while a wall device carries no mark. Detectors are the exception: spot smoke and heat detectors are ceiling devices by their nature, and a W marks the rare one on a wall. Some legends spell out their own convention, which is one reason the legend sheet is read first.
Weatherproof
Exterior and wet-location appliances are a separate, listed model with a weatherproof back box. The drawing marks them WP, sometimes "W/P" or "weatherproof" in a note. A horn/strobe with WP beside it and the same candela as the ones inside is a different line on the order.
Duct smoke detectors
A duct smoke is usually drawn as the smoke detector hexagon with a stem, the line that runs out to the duct it serves, and may sit on the mechanical sheets as well as the fire alarm plans. It has no wall or ceiling mounting in the usual sense and belongs on its own line, not in the smoke detector count. Fire/smoke dampers near it are adjacent equipment, not duct smokes.
Speakers and speaker/strobes
Voice systems tag speakers with a wattage tap (1/4 W, 1/2 W, 1 W, 2 W). A device with both a tap and a candela value is a speaker/strobe; a tap alone is a speaker; a candela value alone is a strobe. On a set with no legend sheet, the labels are what decides the type.
Typical floors
A plan titled "4th and 5th floors (typical)" is one drawing standing for two floors, and a note such as "duct smoke on 5th floor only" means the floors are not identical. Count the sheet once as drawn, list what each floor gets, and show the extended total separately so the person pricing the job can see both numbers.
Status tags on renovation sets
Renovation and tenant-improvement sets mark existing devices, devices to be removed and devices to be relocated with a letter the legend defines (E, M, R and variations). They are still drawn, but they are not all new material. A takeoff should carry the status beside the count, not fold it in.
How Fire Alarm Takeoff reports them
Every device on a counted sheet is ringed on the marked PDF, and the label beside each ring carries its attributes: HS 30 is a horn/strobe at 30 cd on the wall, ST 15 C a ceiling strobe at 15 cd, HS 30 WP the weatherproof one, DS a duct smoke, S a smoke detector. The count grid has one column per kind of device, where a kind is type, candela, mounting and weatherproof together, so "horn/strobe 30 cd wall" and "horn/strobe 30 cd ceiling" are two columns, and the fire-alarm adjacent equipment (tamper and flow switches, dampers, panels, annunciators) sits in its own section with its own total.
- Candela
- Read from the label beside the device. A strobe with no readable candela is listed under "Check these" on the results page so you can read it off the sheet.
- Wall or ceiling
- A C beside or inside the symbol means ceiling; spot detectors are ceiling unless marked W; duct smokes and modules are not applicable. The marking the rule was based on is kept with the device.
- Weatherproof
- A WP mark beside the device. Reported as its own kind of device, so it never merges with the indoor ones.
- Duct smoke
- The stemmed hexagon is a duct smoke detector, its own type and column, even where a legend calls the same symbol something else, unless the legend defines that exact symbol as a damper.
- Speaker and speaker/strobe
- Typed by the legend where there is one, and by the labels (wattage tap, candela) where there is not. The wattage tap itself is not a column.
- Typical floors
- The sheet is counted once as drawn. The grid adds one row per floor the sheet stands for, puts a device restricted by a note on its floor only, and gives a "TOTAL, typical floors extended" under the as-drawn total.
- Status
- Where the legend or your typed symbol notes define a tag such as M for remove, the status is shown beside the label and split out in the totals. No tag means new. The count itself does not change.
- Legend first
- Tick the legend sheet and the set's own symbol definitions override the usual conventions. A type the legend does not define is ringed with a dashed line and a question mark and listed under "Check these".
AI-generated count. Verify before bidding. The attributes are read from the drawing by software, including an AI model, and a tag can be misread as easily as a device can be missed. The label on each ring is there so you can compare it with the tag beside the symbol on the original, sheet by sheet, before the quantities go into a bid.
The fire alarm takeoff guide covers the count as a whole, and the Bluebeam guide explains why a visual search cannot read these tags for you.